Product Details
Transformer Oil Regeneration Machines
Product Code :
TOR-****
Description
Transformer Oil Regeneration Machins
•Regeneration is the procedure followed if oil purification is insufficient to return the oil to an acceptable condition , Regeneration is the restoration of the oil to, or better than, virgin oil specifications.
When to Regenerate
Symptoms
Diagnosis
Treatment
1
Breakdown
Voltage low
Moisture or
solids in oil
Oil Purification
2
Oil colour
orange/brown
Oil deterioration
Oil
Regeneration
3
Visible sludge
in
oil/Transformer
Insulation
Deterioration
Transformer
desluging
4
Free water in oil
or oil cloudy
Insulation
Saturated
Transformer
dry-out
TWO METHODS OF REGENERATIONS
Traditional Fullers Earth
Reactivation
Mothod
Use, Saturate, dispose
Use, saturate, reactivate, etc
Disposal means
Specialist, oily waste
Landfill
Number of Uses
1
300-500
Processing rate
3 gal/ib 25 litre/kg
300 gal/ib 2500 litre/kg
% oil lost
8%
0.4%
Media cost
1
5
Media replaced
weekly
4 years
Equipment cost
1
10
No. of Tower/amount per tower
2/100-400kg
10-60/100kg
Flow rates per tower
High, 4000 lph
Medium=200 lph
Media required to process 1 Million Gal's
200 tons
2 tons
Best suited to
Low volumes, fast, offline
High volumes, slower, energised